BS 6724 cable

The armoured cable with a halogen-free sheath. Same armour as BS 5467, but what comes off it in a fire is smoke and water vapour rather than dense black smoke and acid gas.

0.6/1 kV XLPE · 90 °C SWA LSZH sheath 1.5 – 300 mm²
The standard

What BS 6724 actually specifies

BS 6724 covers thermosetting insulated armoured cables with low emission of smoke and corrosive gases when affected by fire. Read that sentence carefully: the standard is about emissions. It is not about whether the cable keeps carrying current through a fire. Those are two separate properties and two separate pieces of paper.

Structurally, this is a BS 5467 cable with the bedding and the outer sheath swapped from PVC to a halogen-free low-smoke compound. That is the whole difference — and it is also most of the price difference, because the compound costs more and processes more slowly.

i
Low smoke is not fire resistance A cable can be BS 6724 and fail in the first two minutes of a fire. That is not a defect — it is simply a different property. Where the circuit has to keep working — fire alarms, emergency lighting, smoke extraction — the requirement is circuit integrity, tested under BS 6387 or BS 8491, and the cable also needs a product standard behind it. Get both clauses onto the specification, not one.
Standard
BS 6724
Voltage class
600/1000 V (0.6/1 kV)
Conductor
Class 2 stranded copper
Insulation
XLPE — 90 °C continuous
Bedding
Halogen-free compound
Armour
Galvanised steel wire (SWA)
Outer sheath
LSZH, low smoke
Cores
1 to 5 · up to 48 on request
Size range
1.5 – 300 mm²
Unarmoured variant
BS 7211

Emissions limits are set by the IEC test standards listed below, not by a single number in BS 6724. Which ones your project requires determines what evidence you should be asking for.

Side by side

What changes against BS 5467

Two cables, six layers, one substitution. If you are comparing quotations, this is the only column where the difference should appear.

LayerBS 5467BS 6724
ConductorClass 2 stranded copperIdentical
InsulationXLPE, 90 °CIdentical
FillerNon-hygroscopic compoundIdentical
BeddingPVCHalogen-free compound
ArmourGalvanised steel wire (SWA)Identical
Outer sheathPVC, blackLSZH, low smoke
DesignationN2XRYN2XRH
Smoke & acid gasNot controlledControlled to IEC 60754 / 61034
Typical usePlant rooms, sub-mains, direct burialPublic buildings, tunnels, enclosed escape routes
Make "LSZH" mean something

The four test families behind the acronym

"LSZH" on its own is a word. These are the documents that turn it into a specification — and they are exactly what to ask for when a quotation looks too cheap.

TestWhat it measuresWhy it matters on site
IEC 60754-1Halogen acid gas contentHalogen gases form hydrochloric acid with water — it attacks metal structures, switchgear and electronics in the same room.
IEC 60754-2Acidity and conductivity of evolved gasesThe quantitative version. This is the number that proves the compound is genuinely halogen-free rather than "reduced halogen".
IEC 61034Smoke density under the 3 m cube testSmoke, not flame, is what stops people getting out of a building. Measured as light transmittance.
IEC 60332-1-2Flame propagation, single vertical cableThe baseline. A single cable should not carry flame up itself.
IEC 60332-3-22 / -23 / -24Flame propagation, bunched cables, Cat A / B / CThe one that matters in a real cable tray, where cables are touching in a bundle. Categories differ by volume of combustible material.
i
Ask which category, not just "flame retardant" Bunched flame tests are graded A, B and C by the amount of material burnt. A cable passing the single-cable test does not automatically pass the bunched test. If the specification says Cat C and the quotation says "flame retardant", those are not the same claim.
WHERE IT GOES

Applications that drive the requirement

  • High-rise residential and commercial towers
  • Hospitals, schools and retail centres
  • Metro, airport and transport infrastructure
  • Tunnels, basements and enclosed escape routes
  • Data halls and instrumentation rooms
  • Refineries and petrochemical plant
  • Any cable route that shares a shaft with a lift or an exit stair
i
Airports and rail add a second clause Transport infrastructure usually pairs an LSZH requirement with a halogen-free, low-toxicity clause for the same route. If a project cites both, send both — the compounds are not automatically the same.
Get a usable quotation

What a BS 6724 enquiry needs

The construction lines are the same as any armoured LV cable. The extra lines are the ones that decide whether the quotation actually answers your specification.

4 C × 240 mm² ← cores and size
XLPE / SWA / LSZH ← insulation / armour / sheath
600/1000 V ← voltage class
to BS 6724 ← the standard, by number
+ IEC 61034, IEC 60332-3-24 ← the clauses your spec cites

  • Which emission clauses — 60754-1 / -2, 61034, and which 60332-3 category. Name them; don't leave it to "LSZH"
  • Circuit integrity, or not — if the circuit must survive a fire, say so, because it needs a different cable and a different report
  • Quantity and drum length — the achievable maximum length per drum for your size
  • Installation method and ambient — burial, duct or tray, and the site temperature, so the current figures are corrected rather than catalogue
  • Drum marking and test certificates — routine test certificates per drum, and whether you need them in a specific format for the consultant
HONEST NOTE

Where LSZH specifications quietly break

01 · THE WORD WITHOUT THE NUMBER

"LSZH" without a test standard is unverifiable at delivery. If the consultant rejects the drum, there is nothing in the purchase order to appeal to.

02 · SMOKE MISTAKEN FOR SURVIVAL

Life-safety circuits specified as "LSZH" alone will not survive long enough to matter. This is the most expensive mistake on this page, and it is discovered during commissioning.

03 · SHEATH IN PLACE OF REPORT

A halogen-free sheath is a material property. A third-party emissions report is evidence. Projects asking for the evidence should raise it at tender, not at delivery.

Questions we get

BS 6724 — quick answers

Does a low smoke zero halogen cable resist fire?

No — and this is the most common misunderstanding in the whole specification. LSZH describes what the cable emits when it burns: little smoke and no corrosive halogen gas. It says nothing about whether the cable keeps working. That property is circuit integrity, tested under BS 6387 or BS 8491. A cable can be one, the other, or both. Life-safety circuits usually need both.

What is the difference between BS 5467 and BS 6724?

Conductor, XLPE insulation and steel wire armour are the same. The bedding and the outer sheath change from PVC to a halogen-free low-smoke compound. One substitution, two standards. See BS 5467 →

Which test standards should appear on an LSZH quotation?

IEC 60754-1 for halogen acid gas, IEC 60754-2 for acidity and conductivity, IEC 61034 for smoke density, and IEC 60332 for flame propagation — with the 60332-3 series and a category (A, B or C) where cables are bunched. A quotation naming none of these has not yet answered a specification.

Is BS 6724 cable harder to install than BS 5467?

The halogen-free compounds are generally stiffer and less tolerant of tight bends than PVC. Confirm the bending radius for your size rather than assuming it carries over from PVC. On long underground pulls this affects drum set-out and how the run is planned — a planning matter, not a reason to avoid the cable.

Can the armour be left off?

Yes, but it is then a different standard: the unarmoured halogen-free equivalent is BS 7211. Send the installation route — burial, duct, tray — and the right construction follows from that rather than from preference.

Can you supply LSZH in sizes above 300 mm²?

Above 300 mm² it becomes a project question rather than a catalogue one. Send the line with the quantity and we will confirm what is achievable and on what lead time, instead of quoting a size we cannot actually deliver.