LV power cables · building wires · LSZH — specified, not substituted kai@silkoro.com WhatsApp
Home/Products/BS 6387

BS 6387 — fire resistance

The standard behind "fire resistant cable" — except it isn't a cable standard at all. It is a test method. Understanding that distinction is what stops a life-safety circuit being commissioned with the wrong cable in it.

Test standard C · W · Z Circuit integrity Pairs with IEC 60331
Start here

A test standard, not a cable standard

BS 6387 sets out a test method: it describes how to prove that a cable can keep a circuit alive while it is being burnt. It does not say what the cable is made of, how thick the insulation is, or how many cores it has. Those come from a product standard.

So a fire-resistant cable always needs two citations, not one — a product standard that defines the construction, and BS 6387 (or its international counterpart, IEC 60331) that provides the evidence. Papers citing only BS 6387 have named the exam and not the subject.

i
Three things people confuse with each other Flame propagation — does the cable spread fire? Tested to IEC 60332. Emissions — what does it give off when it burns? Tested to IEC 60754 and IEC 61034. Circuit integrity — does it keep working during a fire? Tested to BS 6387 or IEC 60331. Three separate properties, three separate documents. A cable can pass any one and fail another.
Document
BS 6387
Type
Test standard — not a product standard
Property tested
Circuit integrity under fire
Categories
C · W · Z
Combined rating
CWZ
Current edition
2013 — earlier categories withdrawn
International pair
IEC 60331
Large-diameter pair
BS 8491
Needs a product standard
Yes
Typical circuits
Fire alarm, emergency lighting, smoke control

The 2013 revision withdrew the older categories (A, B, S, X and Y) and retained only C, W and Z. An old certificate citing a withdrawn category is not evidence against the current edition — worth checking if a project's paperwork is more than a decade old.

The three protocols

What C, W and Z actually do to the cable

Not three grades — three different disasters. Each one reproduces a specific thing that happens in a real building fire, and each is measured over a different period.

BS 6387 — TEST PROTOCOLS
CategoryTest conditionsSimulates
C Flame at 950 °C for 3 hours, cable carrying its rated voltage. No water, no shock. A sustained fire with no intervention — the baseline case.
W Flame at 650 °C for 15 minutes, then water spray applied for a further 15 minutes. A sprinkler system activating during the fire. Water and heat at once — the condition that cracks a rigid barrier.
Z Flame at 950 °C for 15 minutes, with the cable struck mechanically every 30 seconds. Falling debris, collapsing partitions, the impact of firefighting. The cable is mounted in an S-bend and struck with a bar.
CWZ All three protocols, passed by samples from the same cable. Not a fourth test — a statement that all three were passed.

The pass criterion throughout is the same: the circuit must not fail. Voltage is applied through the cable under load, and a fuse in the circuit must not blow. Note the difference in durations — C runs for three hours, W and Z for fifteen minutes each. They are not comparable by severity.

The trap

CWZ is not a quality ranking

It reads like a badge — three letters, all passed, sounds like the top of a scale. It is not. It means the cable was tested against all three conditions. Whether you need all three depends entirely on the route the cable takes.

Route the cable takesWhat is actually tested for
Protected riser, no sprinklers, no demolition riskFire alone is the governing case — C
Building with a sprinkler system, cable in the same zoneWater during fire matters — W
Route crosses areas subject to collapse or impactMechanical shock matters — Z
Shafts, tunnels, plant rooms, multi-storey escape routesUsually more than one condition applies — hence CWZ in practice

This is a fire engineering decision, not a procurement one. Where the specification is silent, the safe move is to ask the consultant which categories were designed for — before the order, not after the drum is delivered.

PAIRS WITH

Where the requirement usually comes from

  • Fire alarm and detection circuits — must survive long enough to warn
  • Emergency and escape lighting — must survive long enough to be used
  • Smoke and heat control systems — large-diameter cables, often assessed under BS 8491
  • Fire pump supplies — must run while the building is being fought
  • Lifts used for evacuation
  • Pressurised stairwell and lobby systems

All of these also sit inside a building where the same cable run will be specified low-smoke. Expect to see both clauses on the same line item.

i
Product standard, not just test standard A fire-resistant cable also needs a construction standard behind it — the armour, sheath and bedding still have to be defined. Send the full citation as it appears on the specification and both halves will be quoted.
Get a usable quotation

What a fire-performance enquiry needs

Fire-performance cable is the one category where an under-specified enquiry is genuinely dangerous rather than merely inconvenient. Five lines fix it.

4 C × 95 mm² ← cores and size
XLPE / SWA / LSZH ← the product construction
600/1000 V ← voltage class
to BS 6724 ← the product standard
circuit integrity to BS 6387 CWZ ← the test standard and categories

  • Which categories — C, W, Z or CWZ, exactly as the specification writes them
  • Which test standard — BS 6387 or IEC 60331. Not interchangeable citations
  • Whether the evidence is third-party — a supplier's own test data and a report from an accredited laboratory are different documents
  • The emissions clauses too — if it's a life-safety circuit it is almost certainly also specified low-smoke
  • Quantity and drum length, plus the installation route, since route is what determines the category
HONEST NOTE

Where fire-performance procurement goes wrong

01 · THE TEST STANDARD INSTEAD OF THE CABLE

A purchase order reading only "BS 6387 CWZ" has not described a cable. Armour, sheath and cores are all still open, and those are the expensive variables.

02 · A REPORT THAT DOESN'T COVER YOUR SIZE

Fire test reports are issued for a tested construction at a tested size. A report for a small multi-core does not automatically cover a 4 × 95. Always ask what construction and what size the report actually covers.

03 · AN OLD EDITION

Certificates against the pre-2013 categories are citing withdrawn classes. On a project with a strict consultant, that is a rejection at delivery.

Third-party fire tests are arranged per project. Raise the requirement at tender stage and you will get an honest answer on what is achievable and in what timeframe — which is information you need before committing a delivery date.

Questions we get

BS 6387 — quick answers

Is BS 6387 a cable standard?

No. It is a test standard — it describes how to test whether a cable maintains circuit integrity under fire, not what the cable is made of. A fire-resistant cable needs a product standard for the construction and BS 6387 (or IEC 60331) for the evidence. A quotation naming only BS 6387 has named the test.

Does CWZ mean the cable is better than category C?

No, and this is the most common misreading. C, W and Z are different test conditions, not grades. C tests fire alone; W adds water; Z adds mechanical shock. CWZ means all three were passed. Whether you need all three is a property of the route, not of the cable being superior.

What is the difference between BS 6387 and IEC 60331?

The British and international versions of the same test. The 2013 revision of BS 6387 moved closer into line with IEC 60331, but a report to one is not a report to the other. If the specification names one, ask for that one — do not accept the other as equivalent without the consultant's agreement in writing.

What does each category actually test?

C — 950 °C flame for 3 hours, cable under voltage, no water or shock. W — 650 °C flame for 15 minutes, then water spray for 15 minutes, simulating sprinklers. Z — 950 °C flame for 15 minutes with the cable struck every 30 seconds, simulating falling debris. Note the durations differ, so the three are not directly comparable by severity.

Can a cable be fire resistant and low smoke at the same time?

Yes, and on life-safety circuits it usually has to be. They are separate properties with separate documents: circuit integrity to BS 6387 or IEC 60331, emissions to IEC 60754 and IEC 61034. A cable tested to both exists — but only if both were specified in the first place.

What about BS 8491?

BS 8491 is the assessment method for large-diameter power cables used in smoke and heat control systems and similar active fire safety applications. Where a project cites it rather than BS 6387, that is usually a sign the cable is part of a smoke extraction circuit rather than an alarm circuit. Send the citation exactly as written.

Related

Read next

Fire-performance cable on the drawing?

Send the citation exactly as the specification writes it — product standard and test categories. You will get a straight answer on feasibility, and on what evidence can be arranged and when.